US · guidance
CMS SOM App. Z, Tag E-0041
§482.15(e) Condition for Participation:
(e) Emergency and standby power systems. The hospital must implement
emergency and standby power systems based on the emergency plan set forth in
paragraph (a) of this section and in the policies and procedures plan set forth in
paragraphs (b)(1)(i) and (ii) of this section.
§483.73(e), §485.625(e)
(e) Emergency and standby power systems. The [LTC facility and the CAH] must
implement emergency and standby power systems based on the emergency plan set
forth in paragraph (a) of this section.
§482.15(e)(1), §483.73(e)(1), §485.625(e)(1)
Emergency generator location. The generator must be located in accordance with
the location requirements found in the Health Care Facilities Code (NFPA 99 and
Tentative Interim Amendments TIA 12–2, TIA 12–3, TIA 12–4, TIA 12–5, and TIA
12–6), Life Safety Code (NFPA 101 and Tentative Interim Amendments TIA 12–1,
TIA 12–2, TIA 12–3, and TIA 12–4), and NFPA 110, when a new structure is built
or when an existing structure or building is renovated.
482.15(e)(2), §483.73(e)(2), §485.625(e)(2)
Emergency generator inspection and testing. The [hospital, CAH and LTC facility]
must implement the emergency power system inspection, testing, and [maintenance]
requirements found in the Health Care Facilities Code, NFPA 110, and Life Safety
Code.
482.15(e)(3), §483.73(e)(3), §485.625(e)(3)
Emergency generator fuel. [Hospitals, CAHs and LTC facilities] that maintain an
onsite fuel source to power emergency generators must have a plan for how it will
keep emergency power systems operational during the emergency, unless it
evacuates.
*[For hospitals at §482.15(h), LTC at §483.73(g), and CAHs §485.625(g):]
The standards incorporated by reference in this section are approved for
incorporation by reference by the Director of the Office of the Federal Register in
accordance with 5 U.S.C. 552(a) and 1 CFR part 51. You may obtain the material
from the sources listed below. You may inspect a copy at the CMS Information
Resource Center, 7500 Security Boulevard, Baltimore, MD or at the National
Archives and Records Administration (NARA). For information on the availability
of this material at NARA, call 202–741–6030, or go to:
http://www.archives.gov/federal_register/code_of_federal_regulations/ibr_locations.
html.
If any changes in this edition of the Code are incorporated by reference, CMS will
publish a document in the Federal Register to announce the changes.
(1) National Fire Protection Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org
, 1.617.770.3000.
(i) NFPA 99, Health Care Facilities Code, 2012 edition, issued August 11,
2011.
(ii) Technical interim amendment (TIA) 12–2 to NFPA 99, issued August 11,
2011.
(iii) TIA 12–3 to NFPA 99, issued August 9, 2012.
(iv) TIA 12–4 to NFPA 99, issued March 7, 2013.
(v) TIA 12–5 to NFPA 99, issued August 1, 2013.
(vi) TIA 12–6 to NFPA 99, issued March 3, 2014.
(vii) NFPA 101, Life Safety Code, 2012 edition, issued August 11, 2011.
(viii) TIA 12–1 to NFPA 101, issued August 11, 2011.
(ix) TIA 12–2 to NFPA 101, issued October 30, 2012.
(x) TIA 12–3 to NFPA 101, issued October 22, 2013.
(xi) TIA 12–4 to NFPA 101, issued October 22, 2013.
(xiii) NFPA 110, Standard for Emergency and Standby Power Systems, 2010
edition, including TIAs to chapter 7, issued August 6, 2009.
Interpretive Guidelines applies to: 482.15(e), §485.625(e), §483.73(e).
NOTE: For CAHs under §485.625(e)(2) “maintenance” is not included in the
regulatory language.
NOTE: Hospitals, CAHs and LTC facilities are required to base their emergency power
and stand-by systems on their emergency plans and risk assessments, and including the
policies and procedures for hospitals. The determination of the appropriate alternate
energy source should be made through the development of the facility’s risk assessment
and emergency plan. If these facilities determine that a permanent generator is not
required to meet the emergency power and stand-by systems requirements for this
emergency preparedness regulation, then §§482.15(e)(1) and (2), §483.73(e)(1) and (2),
§485.625(e)(1) and (2), would not apply. However, these facility types must continue
to meet the existing emergency power provisions and requirements for their
provider/supplier types under physical environment CoPs or any existing LSC
guidance.
Emergency and standby power systems
CMS requires Hospitals, CAHs and LTC facilities to comply with the 2012 edition of the
National Fire Protection Association (NFPA) 101 – Life Safety Code (LSC) and the 2012
edition of the NFPA 99 – Health Care Facilities Code in accordance with the Final Rule
(CMS–3277–F). NFPA 99 requires Hospitals, CAHs and certain LTC facilities to install,
maintain, inspect and test an Essential Electric System (EES) in areas of a building where
the failure of equipment or systems is likely to cause the injury or death of patients or
caregivers. An EES is a system which includes an alternate source of power, distribution
system, and associated equipment that is designed to ensure continuity of electricity to
elected areas and functions during the interruption of normal electrical service. The EES
alternate source of power for these facility types is typically a generator. (NOTE: LTC
facilities are also expected to meet the requirements under Life Safety Code and NFPA
99 as outlined within the LTC Appendix of the SOM). In addition, NFPA 99 identifies
the 2010 edition of NFPA 110 – Standard for Emergency and Standby Power Systems as
a mandatory reference, which addresses the performance requirements for emergency and
standby power systems and includes installation, maintenance, operation, and testing
requirements.
NFPA 99 contains emergency power requirements for emergency lighting, fire detection
systems, extinguishing systems, and alarm systems. But, NFPA 99 does not specify
emergency power requirements for maintaining supplies, and facility temperature
requirements are limited to heating equipment for operating, delivery, labor, recovery,
intensive care, coronary care, nurseries, infection/isolation rooms, emergency treatment
spaces, and general patient/resident rooms. In addition, NFPA 99 does not require
heating in general patient rooms during the disruption of normal power where the outside
design temperature is higher than 20 degrees Fahrenheit or where a selected room(s) is
provided for the needs of all patients (where patients would be internally relocated), then
only that room(s) needs to be heated. Therefore, EES in Hospitals, CAHs and LTC
facilities should include consideration for design to accommodate any additional
electrical loads the facility determines to be necessary to meet all subsistence needs
required by emergency preparedness plans, policies and procedures, unless the facility’s
emergency plans, policies and procedures required under paragraph (a) and paragraph
(b)(1)(i) and (ii) of this section determine that the hospital, CAH or LTC facility will
relocate patients internally or evacuate in the event of an emergency. Facilities may plan
to evacuate all patients, or choose to relocate internally only patients located in certain
locations of the facility based on the ability to meet emergency power requirements in
certain locations. For example, a hospital that has the ability to maintain temperature
requirements in 50 percent of the inpatient locations during a power outage, may develop
an emergency plan that includes bringing in alternate power, heating and/or cooling
capabilities, and the partial relocation or evacuation of patients during a power outage
instead of installing additional power sources to maintain temperatures in all inpatient
locations. Or a LTC facility may decide to relocate residents to a part of the facility, such
as a dining or activities room, where the facility can maintain the proper temperature
requirements rather than the maintaining temperature within the entire facility. It is up to
each facility to make emergency power system decisions based on its risk assessment and
emergency plan.
If a Hospital, CAH or LTC facility determines that the use of a portable and mobile
generator would be the best way to accommodate for additional electrical loads necessary
to meet subsistence needs required by emergency preparedness plans, policies and
procedures, then NFPA requirements on emergency and standby power systems such as
generator installation, location, inspection and testing, and fuel would not be applicable
to the portable generator and associated distribution system, except for NFPA 70 -
National Electrical Code. (See E-0015 for Interpretive Guidance on portable generators).
Emergency generator location
NFPA 110 contains minimum requirements and considerations for the installation and
environmental conditions that may have an effect on Emergency Power Supply System
(EPSS) equipment, including, building type, classification of occupancy, hazard of
contents, and geographic location. NFPA 110 requires that EPSS equipment, including
generators, to be designed and located to minimize damage (e.g., flooding). The NFPA
110 generator location requirements apply to EPSS (e.g. generators) that are permanently
attached and do not apply to portable and mobile generators used to provide or
supplement emergency power to Hospitals, CAHs and LTC facilities. (See E-0015 for
Interpretive Guidance on portable generators).
Under emergency preparedness, the regulations require that the generator and its
associated equipment be located in accordance with the LSC, NFPA 99, and NFPA 110
when a new structure is built or an existing structure or building is renovated. Therefore,
new structures or building renovations that occur after November 15, 2016, (the effective
date of the Emergency Preparedness Final Rule) must be in compliance with NFPA 110
generator location requirements to be determined as being in compliance with the
Emergency Preparedness regulations.
Emergency generator inspection and testing
NFPA 110 contains routine maintenance and operational testing requirements for
emergency and standby power systems, including generators. Emergency generators
required by NFPA 99 and the Emergency Preparedness Final Rule must be maintained
and tested in accordance with NFPA 110 requirements, which are based on manufacturer
recommendations, instruction manuals, and the minimum requirements of NFPA 110,
Chapter 8.
Emergency generator fuel
NFPA 110 permits fuel sources for generators to be liquid petroleum products (e.g., gas,
diesel), liquefied petroleum gas (e.g., propane) and natural or synthetic gas (e.g., natural
gas). Generators required by NFPA 99 are designated by Class, which defines the
minimum time, in hours, that an EES is designed to operate at its rated load without
having to be refueled. Generators required by NFPA 99 for Hospitals, CAHs and LTC
facilities are designated Class X, which defines the minimum run time as being “other
time, in hours, as required by application, code or user.” The 2010 edition of NFPA 110
also requires that generator installations in locations where the probability of interruption
of off-site (e.g., natural gas) fuel supplies is high to maintain onsite storage of an alternate
fuel source sufficient to allow full output of the ESS for the specified class.
The Emergency Preparedness Final Rule requires Hospitals, CAHs and LTC facilities
that maintain onsite fuel sources (e.g., gas, diesel, propane) to have a plan to keep the
EES operational for the duration of emergencies as defined by the facilities emergency
plan, policy and procedures, unless it evacuates. This would include maintaining fuel
onsite to maintain generator operation or it could include making arrangements for fuel
delivery for an emergency event. If fuel is to be delivered during an emergency event,
planning should consider limitations and delays that may impact fuel delivery during an
event. In addition, planning should ensure that arranged fuel supply sources will not be
limited by other community demands during the same emergency event. In instances
when a facility maintains onsite fuel sources and plans to evacuate during an emergency,
a sufficient amount of onsite fuel should be maintained to keep the EES operational until
such time the building is evacuated.
For information regarding permanently installed generators, please refer to applicable
NFPA Codes and Standards as discussed under Tag E-0015. In the event a health
surveyor is unclear whether the facility is complying with these requirements, the health
surveyor must consult with their LSC surveyors. Generally, tag E-0041 should be
reviewed by a LSC surveyor.
Survey Procedures
• Verify that the hospital, CAH and LTC facility has the required emergency and
standby power systems to meet the requirements of the facility’s emergency plan and
corresponding policies and procedures.
• Review the emergency plan for “shelter in place” and evacuation plans. Based on
those plans, does the facility have emergency power systems or plans in place to
maintain safe operations while sheltering in place?
• For hospitals, CAHs and LTC facilities which are under construction or have existing
buildings being renovated, verify the facility has a written plan to relocate the EPSS
by the time construction is completed.
For hospitals, CAHs and LTC facilities with permanently attached generators:
• For new construction that takes place between November 15, 2016 and is completed
by November 15, 2017, verify the generator is located and installed in accordance
with NFPA 110 and NFPA 99 when a new structure is built or when an existing
structure or building is renovated. The applicability of both NFPA 110 and NFPA 99
addresses only new, altered, renovated or modified generator locations.
• Verify that the hospitals, CAHs and LTC facilities with an onsite fuel source
maintains it in accordance with NFPA 110 for their generator, and have a plan for
how to keep the generator operational during an emergency, unless they plan to
evacuate.
History
Rev. 204, Issued: 04-16-21; Effective: 04-16-21, Implementation: 04-16-21
Provenance
- Source
- cms.gov
- Retrieved
- 2026-07-22
- Edition
- som-2026-07-22
- Content hash
a318aa87d39fbe57728bc18345b4d59d5f9ac9271828d6390648218a2f03eb4c
The link goes to the issuing authority’s own document — the one we read to produce this record. Where a source publishes whole titles rather than sections, your browser may need a moment to jump to the provision.
Unofficial copy of government-published law, reproduced from official sources with full provenance. Not an official publication; verify against official sources before relying on it in a filing. Records in the 'guidance' corpus, and only that corpus, are sub-regulatory (interpretive guidelines, survey procedures) and are not binding law. Validity bounds follow each jurisdiction's declared temporalBasis.