§403.744(a) General
An RNHCI must meet the following conditions:
(1) Except as provided in this section-
(i) Notwithstanding paragraph (a)(1)(i) of this section, corridor doors and
doors to rooms containing flammable or combustible materials must be
provided with positive latching hardware. Roller latches are prohibited
on such doors.
Interpretive Guidelines: §403.744 (a)(1)(ii)
Corridor doors and doors to rooms containing flammable or combustible materials must
be provided with hardware that has a latch to keep the door in a closed position. Roller
latches, which will release by pushing on the door, are prohibited on such doors.
Survey Procedure:
The LSC surveyors will assess the corridor doors and doors to hazardous areas during
the LSC survey. However, if health surveyors find questionable door closures, this
should be discussed with the LSC surveyor.
History
Rev. 239; Issued: 04-24-26; Effective: 04-24-26; Implementation: 04-24-26
Provenance
- Source
- cms.gov
- Retrieved
- 2026-07-22
- Edition
- som-2026-07-22
- Content hash
607b609f543a9ede6c0613adedc93f986b2720a6991a48aee1d6eab9e004433c
The link goes to the issuing authority’s own document — the one we read to produce this record. Where a source publishes whole titles rather than sections, your browser may need a moment to jump to the provision.
Unofficial copy of government-published law, reproduced from official sources with full provenance. Not an official publication; verify against official sources before relying on it in a filing. Records in the 'guidance' corpus, and only that corpus, are sub-regulatory (interpretive guidelines, survey procedures) and are not binding law. Validity bounds follow each jurisdiction's declared temporalBasis.