CMS SOM App. U, Tag R211
(ii) Measure at least 80 square feet per patient in multiple patient rooms and at
least 100 square feet in single patient rooms.
Interpretive Guidelines: §403.742(b)(1)(ii)
The measurement of the square footage should be based upon the useable living space of
the room. Therefore, the minimum square footage in patient rooms should be measured
based upon the floor’s measurements exclusive of toilets and bath areas, closets, lockers,
wardrobes, alcoves, or vestibules. However, if the height of the alcoves or vestibules
reasonably provides useful living area, then the corresponding floor area may be included
in the calculation.
The space occupied by movable wardrobes should be excluded from the useable square
footage in a room, unless it is an item of the patient’s own choice, and it is in addition to
the individual closet space in the patient’s room. Non-permanent items of the patient’s
own choice should have no effect in the calculation of useable living space.
Protrusions such as columns, radiators, ventilation systems for heating and/or cooling
should be ignored in computing the useable square footage of the room if the area
involved is minimal (e.g., a baseboard heating or air conditioning system or ductwork
that does not protrude more than 8 inches from the wall, or a column that is, not more
than 8 inches on each side), and does not have an adverse effect on the patient’s health
and safety. If these protrusions are not minimal, they would be deducted from useable
square footage computed in determining compliance with this requirement.
The swing or arc of any door that opens directly into the patient’s room should not be
excluded from the calculations of useable square footage in a room.
Survey Procedures:
• The majority of the RNHCI rooms are generally single patient rooms. However, if
the surveyor determines the room appears small, take measurements.
• If the measurements of the small room result in a deficiency with the requirement,
request a floor plan which includes square footage and/or sample at least 3
patient rooms to confirm this is not a systemic issue within the facility.
• Unless a variance has been applied for and approved as at §403.742(b)(3), are
there at least 80 square feet per patient in multiple patient rooms and at least 100
square feet for single patient rooms?
History
Rev. 239; Issued: 04-24-26; Effective: 04-24-26; Implementation: 04-24-26
Provenance
- Source
- cms.gov
- Retrieved
- 2026-07-22
- Edition
- som-2026-07-22
- Content hash
f5c5244c5248d2cf40215b5a5c5a4796f3d5b7da14b65903cf1c6aa60de4a601
The link goes to the issuing authority’s own document — the one we read to produce this record. Where a source publishes whole titles rather than sections, your browser may need a moment to jump to the provision.
Unofficial copy of government-published law, reproduced from official sources with full provenance. Not an official publication; verify against official sources before relying on it in a filing. Records in the 'guidance' corpus, and only that corpus, are sub-regulatory (interpretive guidelines, survey procedures) and are not binding law. Validity bounds follow each jurisdiction's declared temporalBasis.