§ 494.60(d) - Standard: Fire safety
(1) Except as provided in paragraph (d)(2) of this
section, dialysis facilities that do not provide one or more exits to the outside at grade level
from the patient treatment area level, must comply with provisions of the 2012 edition of
the Life Safety Code of the National Fire Protection Association (NFPA 101 and tentative
interim amendments TIA 12-1, TIA 12-2, TIA 12-3, and TIA 12-4) applicable to
Ambulatory Health Care Occupancies [which is incorporated by reference in paragraph (f)
of this section], regardless of the number of patients served.
Interpretive Guidance § 494.60(d)(1)
ESRD facilities that do not provide one or more exits to the outside at grade level from the
patient treatment area must comply with the requirements contained in the 2012 edition of the
Life Safety Code (NFPA 101) and the Tentative Interim Amendments TIA 12-1, TIA 12-2, TIA
12-3 and TIA 12-4 applicable to the Ambulatory Health Care Occupancies, regardless of the
number of patients served.
Dialysis facilities that provide one or more exits to the outside at grade level would be exempt
from meeting the requirements in the 2012 edition of the Life Safety Code (NFPA 101) and the
applicable tentative interim amendments. Exempt facilities must continue to comply with state
and local fire codes.
Page 176 of 420
“Exit to the outside at grade level from the patient treatment area level” is to mean that ESRD
facilities are on the ground or grade level of a building where patients do not have to traverse up
or down stairways to evacuate to the outside. Accessibility ramps in the exit area that provide an
ease of access between the patient treatment level and the outside ground level are not
considered stairways.
A dialysis facility required to comply with the LSC must operate in accordance with the code
chapters (Chapters 20 or 21) applicable to ambulatory health care occupancies. However, a
dialysis facility may be located in a mixed occupancy building. If a dialysis facility is located in
a building with other tenants and occupancies, it must be separated by a one-hour fire-resistance-rated wall in accordance with the LSC. For purposes of this regulation, when a
portion of the dialysis facility is used intermittently by another entity (e.g., an exam room is used
for the nephrologist’s office practice) it is not intended that the portion used intermittently would
be separated from the dialysis facility by a one-hour fire wall.
If the dialysis facility is located within a hospital, but not separated from the hospital by two-hour fire wall construction, the dialysis facility must meet the hospital LSC requirements. If a
hospital-based chronic outpatient facility provides acute services for hospitalized patients in the
same space and within the hospital walls, the outpatient dialysis facility must meet the more-stringent hospital chapters of the LSC.
Survey instructions found in State Operations Manual (SOM), Appendix I, are used as
applicable, along with the Fire Safety Survey Report Form, 2786U to survey for fire safety. The
fire safety standard will be surveyed by a fire specialist from the State Agency or a CMS-approved Accrediting Organization, if accredited; generally, the LSC inspections will be done
separately from the rest of the ESRD facility survey.
History
Rev.
Provenance
- Source
- cms.gov
- Retrieved
- 2026-07-22
- Edition
- som-2026-07-22
- Content hash
75329a949f1aa7be68779a7bbcb363bb2c6dd5f954864984313529065b17af01
The link goes to the issuing authority’s own document — the one we read to produce this record. Where a source publishes whole titles rather than sections, your browser may need a moment to jump to the provision.
Unofficial copy of government-published law, reproduced from official sources with full provenance. Not an official publication; verify against official sources before relying on it in a filing. Records in the 'guidance' corpus, and only that corpus, are sub-regulatory (interpretive guidelines, survey procedures) and are not binding law. Validity bounds follow each jurisdiction's declared temporalBasis.