US · guidance
CMS SOM App. A, Tag A-0718
§482.41(b)(9) Buildings must have an outside window or outside door in every sleeping
room, and for any building constructed after July 5, 2016 the sill height must not exceed 36
inches above the floor. Windows in atrium walls are considered outside windows for the
purposes of this requirement.
(i) The sill height requirement does not apply to newborn nurseries and rooms intended for
occupancy for less than 24 hours.
(ii) The sill height in special nursing care areas of new occupancies must not exceed 60
inches.
Interpretive Guidelines §482.41(b)(9):
Every patient sleeping room shall have an outside window or door. Rooms intended for less
than 24 hours occupancy (e.g., recovery, delivery, emergency care, nursery, etc.) do not require
outside windows or doors. Windows in atrium walls are considered outside windows for the
purpose of this requirement.
In buildings constructed after July 5, 2016, the maximum allowable sill height is 36 inches above
the floor, except in special nursing areas (e.g., recovery rooms, intensive care units, coronary
care units, etc.) where the sill height can be up to 60 inches.
Survey Procedures §482.41(b)(9):
Identify patient sleeping rooms intended to be occupied for more than 24 hours. Confirm these
rooms have an outside window or outside door. If the building was constructed after July 5,
2016, confirm the outside window sill is 36 inches or less above the floor. In newly constructed
special nursing areas, confirm the outside window is 60 inches or less above the floor.
History
Rev. 238; Issued: 03-20-26; Effective: 09-05-25; Implantation: 09-05-25
Provenance
- Source
- cms.gov
- Retrieved
- 2026-07-22
- Edition
- som-2026-07-22
- Content hash
29e32b1a311b878e86feb94eeb083f98385bd7fc0485b11be102454f40a5fffc
The link goes to the issuing authority’s own document — the one we read to produce this record. Where a source publishes whole titles rather than sections, your browser may need a moment to jump to the provision.
Unofficial copy of government-published law, reproduced from official sources with full provenance. Not an official publication; verify against official sources before relying on it in a filing. Records in the 'guidance' corpus, and only that corpus, are sub-regulatory (interpretive guidelines, survey procedures) and are not binding law. Validity bounds follow each jurisdiction's declared temporalBasis.