US · guidance
BOP Program Statement 1600.16 § 22
INSPECTION, TESTING, AND MAINTENANCE
a. Weekly Inspections. Weekly fire protection and life safety inspections must be conducted
by the IDO. Specific items covered must be outlined in the institution’s Fire Plan.
b. Monthly Inspections. The SA ensures monthly fire protection and life safety inspections are
conducted. Specific items covered must be outlined in the Fire Plan.
c. Outside Fire Agency Visits. An invitation to conduct a courtesy visit must be extended to
responding fire agencies annually. Any outside fire agency recommendations should be reviewed
by the SA and implemented, if practical.
d. Annual Inspection. An annual fire protection and life safety inspection must be conducted
by one of the following:
SA
RSA
Central Office Occupational Safety and Health Branch staff
1600.16 6/22/2026 PROPERTY OF US GOVERNMENT 32
e. Fire Alarm System Inspections. Alarm systems must be inspected, tested, and maintained
in accordance with NFPA 72, by qualified Facilities staff or an outside contractor.
f. Sprinklers, Standpipes, Hydrants, Tanks, and Other Water-Based Extinguishing System
Inspections. Water-based extinguishing systems must be inspected, tested, and maintained per
NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire
Protection Systems by qualified Facilities staff or an outside contractor.
In addition to the tests specified in NFPA 25, quarterly main drain tests must be conducted by
qualified Facilities staff or a qualified outside contractor on all sprinkler risers.
An annual sprinkler inspection must be conducted by a qualified outside contractor. Other
inspections and tests may be conducted by qualified Facilities staff.
Any time a sprinkler system control valve is closed, a main drain test must be conducted as soon
as the valve is re-opened.
g. Fire Hydrant Test. Fire hydrants on institution property must be flow-tested annually. Tests
must be conducted by qualified Facilities staff or an outside contractor.
h. Underground and Exposed Piping Test. A full flow test of underground and exposed
piping serving fire hydrants must be conducted at least every five years. Tests must be
conducted by qualified Facilities staff or an outside contractor.
i. Kitchen Hood and Duct System Inspection. Exhaust systems, along with associated fixed
fire suppression systems, must be inspected, tested, and maintained in accordance with NFPA 96,
Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations.
j. Portable Fire Extinguisher Inspection. Extinguishers must be inspected, tested, and
maintained in accordance with NFPA 10, Standard for Portable Fire Extinguishers. Annual
maintenance/inspection must be conducted by a certified staff member or contractor.
k. Halon Extinguishing System. Existing Halon 1301 systems must be inspected, tested, and
maintained in accordance with NFPA 12A, Standard on Halon 1301 Fire Extinguishing Systems.
Portable Extinguishers. Portable Halon fire extinguishers are not permitted
Fixed Halon Systems. New fixed Halon fire suppression may not be installed
l. Inspection Records. Inspections must be documented by a written report:
Weekly/Monthly Inspections. Written reports of weekly and monthly inspections,
including deficiencies, must be sent to the Department Head and forwarded to the
1600.16 6/22/2026 PROPERTY OF US GOVERNMENT 33
Warden, through the Associate Warden, for review and corrective action, if needed. The
reports and corrective actions taken must be kept in the Occupational Safety & Health
Department for three years.
Fire Alarm/Suppression Inspections. Inspection, testing, and maintenance records for
fire detection, alarm, and suppression equipment must be kept for three years.
Hydrostatic Testing. Records of hydrostatic testing must be kept until the next test.
m. SCBA. SCBA must be inspected, tested, and maintained as follows:
Monthly inspection by Occupational Safety and Health Department staff
Annual inspection by a manufacturer’s authorized service representative
Annual regulator flow test by a manufacturer’s authorized service representative
Air cylinders must be re-tested in accordance with the appropriate U.S. Department of
Transportation (DOT) specification or the applicable DOT exemption.
Carbon fiber air cylinders must be re-tested every five years
Carbon fiber air cylinders have a maximum 15-year or 30-year service life depending
on the model
Inspection, testing, and maintenance records must be maintained by the Occupational
Safety and Health Department
History
PS 1600.16 dated 2026-06-22
Provenance
- Source
- bop.gov
- Retrieved
- 2026-09-20
- Edition
- bop-ps-2026-09-20
- Content hash
53d33373d3da63865d346451d5af43aea266127bbacbf6ee780814baee23be0d
The link goes to the issuing authority’s own document — the one we read to produce this record. Where a source publishes whole titles rather than sections, your browser may need a moment to jump to the provision.
Unofficial copy of government-published law, reproduced from official sources with full provenance. Not an official publication; verify against official sources before relying on it in a filing. Records in the 'guidance' corpus, and only that corpus, are sub-regulatory (interpretive guidelines, survey procedures) and are not binding law. Validity bounds follow each jurisdiction's declared temporalBasis.