US · guidance
BOP Program Statement 1600.16 § 19
FIRE SUPPRESSION/DETECTION SYSTEMS
a. Sprinkler Systems (Installation). All new buildings, additions, and renovations must be
protected by a sprinkler system. The AHJ may approve non-sprinklered additions to existing non-sprinklered buildings on a case-by-case basis.
Exception. Small buildings outside the secure perimeter, towers, shooting range buildings, and
range canopies are not required to be protected by a sprinkler system unless specifically
mandated by Bureau policy, Building Codes, or NFC.
b. Sprinkler System (Design). New sprinkler systems must be designed and installed in
accordance with the most recent edition of NFPA 13, Standard for the Installation of Sprinkler
Systems.
c. Sprinkler System (Modification). Sprinkler system modifications must be made in
accordance with the most recent edition of NFPA 13.
d. Sprinkler System (Reevaluation). Any change in the sprinkler system, building, storage
arrangement, or water supply must be accompanied by a reevaluation of the sprinkler system
adequacy.
e. Sprinkler System (Approval). Approval to continue using a building after modifications
have been made to the sprinkler system, building, storage arrangement, or water supply must be
issued by the SA.
f. Sprinkler System (Existing Buildings). The following existing buildings/areas must be
protected by a sprinkler system:
■ Inmate housing units
■ Storage areas with high hazard contents
■ Buildings mandated by a regulatory requirement
g. Sprinkler System (Supervision). The following conditions must be supervised on all
sprinkler systems:
Water flow
Valve position
h. Sprinkler System (Monitoring). The following sprinkler system components must be
monitored through the fire alarm in the Control Center:
Water flow alarms
1600.16 6/22/2026 PROPERTY OF US GOVERNMENT 26
Valve tamper switches
i. Sprinkler System (SHU Cell Isolation Valves). Up to four cells per SHU range may be
equipped with isolation valves to control the operation of sprinklers in an individual cell. The
SHU cell sprinkler control valves must be:
Indicating valves
Easily accessible
Locked in the open position
Inspected monthly by Facilities staff
Sprinkler valves isolating the head(s) in a SHU individual cell do not require valve tamper
supervision.
j. Sprinkler System (Special Housing Unit [SHU] Cell Isolation Valve Procedures). The
following procedures allow the sprinkler(s) for a single cell in SHU to be temporarily shut off:
Operations Lieutenant must notify the SA
All combustible contents must be removed from the cell
Cell isolation valve is shut but not secured in the closed position
Record the valve closure reason and time in both the Control Center and SHU logs
Notify the Control Center the valve has been closed
Notify SHU staff the valve has been closed
Establish a procedure to immediately open the valve in the event of fire
k. Standpipe System (Installation). New multistory inmate housing areas must be equipped
with standpipe systems to supply water for a fire response by trained personnel.
l. Standpipe System (Hose). Pre-connected hose is not required for standpipes in sprinklered
buildings. Each institution must maintain a supply of centrally located hose, nozzles, fittings, and
tools to be available for use by staff or trained response personnel.
m. Standpipe System (Existing Non-Sprinklered Inmate Housing Areas). Existing non-sprinklered inmate housing areas must be equipped with a standpipe system.
n. Standpipe System (Non-Sprinklered Hose Requirement). Hose must be provided and
available at all standpipe system connections in non-sprinklered inmate housing areas.
o. Standpipe System (Cabinets). Standpipe cabinets may be locked if staff working in or
responding to the area have the necessary keys to open the cabinets.
1600.16 6/22/2026 PROPERTY OF US GOVERNMENT 27
p. Fire Extinguisher (Installation). Portable fire extinguishers must be installed throughout the
facility. Extinguisher locations, inspection, testing, and maintenance must be in accordance with
NFPA 10, Standard for Portable Fire Extinguishers.
Exception (Inmate Housing Areas Only). NFPA 101 allows portable fire extinguishers to be
located in “staff only” areas. This allowance may result in travel distances that exceed those
permitted by NFPA 10. It is critical the spacing of fire extinguishers be maintained as close as
practical to the NFPA 10 travel limits. In addition, consolidating extinguishers into a single area,
such as an officers’ station, without regard for the travel limits, is not permitted. The location of
fire extinguishers must be approved by the SA.
q. Fire Extinguisher (Cabinets). Fire extinguishers in areas subject to tampering or
unauthorized use may be installed in cabinets:
Cabinets may have solid front doors
Cabinets may be locked if staff working in or responding to the area have the necessary
keys to open them
Cabinets installed in fire-rated wall assemblies must have the correct fire protection
rating
Cabinets with a fire protection rating must not be altered
r. Fire Extinguisher (Class K). Class K fire extinguishers must be provided for the protection
of cooking appliances that use combustible cooking media (e.g., vegetable or animal oils and
fats).
s. Fire Extinguisher (Class K Signage). Where cooking appliances that use combustible
cooking media are protected by an automatic fire suppression system, a placard must be
conspicuously placed near the class K fire extinguisher that states the fire suppression system
must be actuated prior to using the extinguisher.
t. Fire Extinguisher (Class K Travel Distance). The maximum travel distance from the
combustible cooking media hazard to the class K extinguisher(s) must not exceed 30 feet.
u. Kitchen (Hood and Duct Exhaust Systems). Institution cooking equipment must be
protected by a hood and duct system that is designed, installed, operated, and maintained in
accordance with NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial
Cooking Operations.
Exemption. The following cooking operations are exempt from the hood and duct exhaust
system requirement:
Stand-alone microwave ovens
1600.16 6/22/2026 PROPERTY OF US GOVERNMENT 28
Limited-use kitchens
v. Kitchen (Hood and Duct Fire-Suppression System). The following must be protected by a
fire suppression system:
Exhaust hoods
Exhaust ducts
Grease removal devices
Cooking equipment that may produce grease-laden vapors
w. Kitchen (Hood and Duct Suppression System Service). The fixed fire suppression systems
protecting cooking operations must be serviced by a competent outside contractor at least every
six months.
x. Kitchen (Hood and Duct Exhaust System Cleaning Service). Hood and duct exhaust
systems must be cleaned as often as needed to prevent a build-up of grease. The maximum time
between cleanings must not exceed 12 months.
y. Kitchen (Cooking Equipment). All institution cooking equipment must be certified by
National Sanitation Foundation (NSF) International.
z. Kitchen (Cooking Equipment Installation and Maintenance). Cooking equipment
installation and repairs must be performed by qualified personnel.
aa. Fire Alarm Systems. Fire alarm systems must be installed in all areas mandated by:
NFC
Building codes
Bureau policy
bb. Fire Alarm Systems (Locked Buildings). Buildings that can be locked to restrict egress
must be equipped with a fire alarm system that can be activated by manual pull stations.
cc. Fire Alarm Systems (Out Buildings). Fire alarm systems are not required in small buildings
outside the secure perimeter unless mandated by the NFC, Building Code, or Bureau policy.
dd. Fire Alarm Systems (Inmate Housing Area Pull Stations). Manual fire alarm pull stations
are required in inmate housing areas. Pull stations must be located in accordance with NFPA 72,
National Fire Alarm and Signaling Code.
Pull stations may be locked if staff working in and/or responding to the area, have the keys
necessary to activate the fire alarm system.
1600.16 6/22/2026 PROPERTY OF US GOVERNMENT 29
Manual pull stations may be located in the officers’ station, provided:
The officers’ station is attended when the building is occupied
The officers’ station provides a direct line of sight over the entire unit
ee. Fire Alarm Systems (Smoke Detection Systems). Smoke detectors must be installed in all
areas mandated by:
NFC
Building codes
Bureau policy
ff. Fire Alarm Systems (Large Cells/Sleeping Areas). Cells and sleeping areas with five or
more occupants must be equipped with smoke detectors.
gg. Fire Alarm Systems (Supervision). Fire alarm systems must be supervised by the Control
Center staff.
hh. Fire Alarm Systems (Annunciator Panels). The main fire alarm annunciator panel must be
checked on each shift by Control Center staff. Annunciator panels in other areas must be checked
on each shift by the staff member supervising the area.
Institution Duty Officer (IDO) must check the main fire alarm annunciator panel as part of the
weekly fire, safety, and sanitation inspection.
ii. Fire Alarm Systems (Trouble/Alarms). Trouble/alarm conditions on fire alarm systems
must be reported to the SA and Facilities Manager.
jj. Fire Alarm Systems (Control Center Staff Competencies). Staff working in the Control
Center must be competent in the operation of the fire alarm system and alarm annunciator panel.
kk. Fire Alarm System (Instruction Booklet). An instruction booklet outlining the operation
of the fire alarm system and the alarm annunciator panels must be available in the Control Center
at all times.
ll. Fire Alarm Systems (Fire Department Notification). Staff working in the Control Center
must immediately notify the local fire department in event of a fire. Notification may be delayed
up to 90 seconds while staff verify an alarm from a single smoke detector.
The fire department must be notified immediately if a second alarm (e.g., water flow, heat
detectors, manual pull station) is received.
1600.16 6/22/2026 PROPERTY OF US GOVERNMENT 30
mm. Fire Alarm System (Malfunction). The following actions must be taken when a
malfunction of the fire alarm system is detected:
Notify the Operations Lieutenant
Notify the Facilities Department
Notify the Occupational Safety and Health Department
Make an entry in the Control Center log
nn. Emergency Phone List. Staff working in the Control Center must have immediate access to
emergency telephone numbers, including the local fire department.
oo. Fire Department Entry. Fire department authorization to enter the institution must be
determined by the incident commander based on:
Security considerations
Severity of the incident
A written emergency response procedure outlining entry and escort protocols must be
established with the local fire department as part of the Fire Plan.
History
PS 1600.16 dated 2026-06-22
Provenance
- Source
- bop.gov
- Retrieved
- 2026-09-20
- Edition
- bop-ps-2026-09-20
- Content hash
229d75b71852017d189e9ca2dd09dca08ad716da717f7bc24832ece15cf0cd55
The link goes to the issuing authority’s own document — the one we read to produce this record. Where a source publishes whole titles rather than sections, your browser may need a moment to jump to the provision.
Unofficial copy of government-published law, reproduced from official sources with full provenance. Not an official publication; verify against official sources before relying on it in a filing. Records in the 'guidance' corpus, and only that corpus, are sub-regulatory (interpretive guidelines, survey procedures) and are not binding law. Validity bounds follow each jurisdiction's declared temporalBasis.